kVA Calculator

Enter your voltage and whichever one of kVA, kW or amps you already know, and this works out the other two for single or three phase. It also shows why three phase carries a square root of 3, and why a generator sold as 100 kVA is only offered as 80 kW.

Fill in just one of these three and leave the other two blank.

Put this calculator on your website for free

Copy one snippet and give your visitors a working kVA Calculator.

What kVA actually measures

kVA is apparent power: everything the supply has to push down the wire. kW is real power: the part that turns into heat, light or motion at the far end. In a purely resistive load, a heater or an old filament lamp, the two are identical. Add anything with a magnetic field or a switching supply, which means essentially every motor, transformer and drive, and some of the current spends its time going back and forth without doing anything useful. The ratio of the useful part to the total is the power factor.

That gap is not academic, because it decides which number you size things from. Cables, breakers, transformers, UPS units and generators all have to carry the whole current, whether or not it does any work when it arrives. So every one of them is rated in kVA. Your load schedule, your energy bill and your engine's fuel burn all track the work actually done, so they are in kW. Two numbers, both correct, describing the same installation, and typically 20 to 25 percent apart.

The formula

single phase: kVA = V × I ÷ 1000
three phase: kVA = √3 × V × I ÷ 1000
kW = kVA × power factor

V is the supply voltage, which for three phase means the line to line figure printed on the nameplate (208, 400 or 480 rather than 120, 230 or 277). I is the current in one line conductor. Note that the power factor appears in the kW line and nowhere in the current line: it changes how much work the current does, not how much current there is.

Where the square root of 3 comes from

The 1.732 gets memorised and almost never explained, and because it makes the answer bigger, a lot of people quietly assume it is a safety margin or an efficiency. It is neither. It is geometry.

In a balanced three-phase system the three voltages are 120 degrees apart. Measure between two lines rather than between a line and neutral and you are adding two vectors at 120 degrees, which gives you √3 times the line-to-neutral voltage. So the total apparent power is three conductors each carrying Vphase × I, and substituting Vphase = Vline ÷ √3 turns 3 into 3 ÷ √3, which is √3. That is the whole derivation: the square root of 3 is just 3 divided by the square root of 3.

The practical payoff is that at the same voltage and current, three phase moves 73 percent more power than a single-phase pair does, which is why anything above a few tens of kW is three phase almost everywhere in the world.

Worked example

A 100 kVA three-phase supply at 400 V, power factor 0.80.

The multiplier is √3 × 400 = 692.8.

Current: 100 × 1000 ÷ 692.8 = 144.3 A in each line.

Real power: 100 × 0.80 = 80 kW.

Reactive power: √(100² − 80²) = √3600 = 60 kVAR, exactly.

That last one is a small gift from the arithmetic. At a power factor of 0.8 the power triangle is a 3-4-5 triangle: 60, 80 and 100. It is the same triangle from school geometry, which makes 0.8 an unusually easy power factor to sanity-check in your head.

Why a 100 kVA generator is an 80 kW generator

This is the single most expensive misunderstanding in the subject, and it is nobody's fault: both numbers are printed, both are honest, and quotes rarely say which one they mean.

Generator sets are rated at a power factor of 0.8 lagging by convention, which is what ISO 8528 assumes. So a set advertised as 100 kVA is offered as 80 kW, and a genuinely 100 kW machine is a 125 kVA set. If you add up a load schedule in kW and then shop for a generator with the same number on it, you will buy one 25 percent too small, and you will not find out until the day it is actually needed.

The honest comparison is kW against kW, or kVA against kVA, with your own power factor used to move between them. This calculator prints both figures side by side for exactly that reason. Worth adding: on most real installations it is motor starting, not running load, that decides the size, because a motor can draw six or seven times its running current for a few seconds. Running totals tell you what the machine must sustain; starting surge tells you what it must survive.

The number worth improving rather than just measuring

Power factor is one of the few figures in an electrical installation you can genuinely change. Here is roughly what different loads look like:

LoadTypical power factorWhat that means for a 100 kVA supply
Heaters, filament lighting1.00100 kW of work
Modern electronics with correction0.9595 kW of work
Well-loaded motors0.8585 kW of work
Generator rating convention0.8080 kW of work
Lightly loaded motors0.5050 kW of work

Read the right-hand column again: the same 100 kVA supply does anything from 50 kW to 100 kW of useful work depending entirely on what you hang off it. An oversized motor running at a quarter load is the classic case, and it is why "just fit a bigger one to be safe" can quietly halve the capacity of a switchboard.

Capacitors can correct a lagging power factor and free up real capacity without pulling any new cable, which is often much cheaper than upgrading a supply. Many commercial tariffs also charge for poor power factor directly, so the improvement can show up twice. It is worth getting an electrician to measure yours rather than assuming, since the number you actually have is usually better than 0.8 and occasionally a good deal worse.

Frequently asked questions

What is the difference between kVA and kW?

kVA is apparent power, the total the supply has to deliver. kW is real power, the part that does useful work. The ratio between them is the power factor, so kW = kVA x power factor. Cables, breakers, transformers and generators are all sized from the kVA, because the whole current flows through them whether or not it does any work at the far end.

How do I convert kVA to amps?

For single phase, amps = kVA x 1000 / volts. For three phase, amps = kVA x 1000 / (1.732 x volts), where the voltage is the line to line figure. Power factor does not appear in either one, which surprises people: it changes how much work the current does, not how much current there is.

Why is there a square root of 3 in three-phase calculations?

Because line to line voltage is the square root of 3 times line to neutral voltage, and three conductors share the load. Total apparent power is 3 x Vphase x I, and substituting Vphase = Vline / root 3 leaves root 3 x Vline x I. So the 1.732 is 3 divided by root 3. It is geometry from the 120 degree spacing between phases, not an efficiency or a safety margin.

What size generator do I need in kVA?

Take your total load in kW, divide by your actual power factor to get kVA, and then compare against the generator's kVA rating rather than its kW rating. Generator sets are rated at 0.8 power factor by convention, so a 100 kVA set is offered as 80 kW. Motor starting usually decides the answer rather than running load, so size the surge as well.

Is a 100 kVA generator the same as a 100 kW generator?

No, and the gap is 20 percent. A 100 kVA set rated at the standard 0.8 power factor delivers 80 kW of real power. A machine genuinely rated 100 kW would be a 125 kVA set. Both numbers are printed on nameplates and marketing material, so it is worth checking which one a quote is using before comparing two of them.

What is a typical power factor?

Resistive loads like heaters and incandescent lighting sit at or very near 1.0. Motors typically run 0.8 to 0.9 when loaded and drop well below that when lightly loaded, which is one reason an oversized motor is an expensive motor. Modern electronics with power factor correction reach 0.95 or better. If you do not know yours, 0.8 is the conventional planning figure and it is deliberately pessimistic.

What is kVAR and does it matter?

kVAR is reactive power, the part of the apparent power that does no work. It is the third side of the power triangle: kVA squared equals kW squared plus kVAR squared. It matters because it still occupies your cables and transformer, and because many commercial tariffs charge for a poor power factor. Correcting it with capacitors is a standard way to free up capacity without new cable.

Should I size cable from kVA or kW?

From the kVA, always, because the conductor carries the whole current regardless of how much of it turns into work. Sizing from kW at a power factor of 0.8 would understate the current by 25 percent, which is enough to pick the wrong cable and the wrong breaker. This calculator reports the current so you do not have to make that choice.

Related calculators